Shanghai DEMIKS Electric Power Technology Co.,LTD

Three-phase transformer turndown ratio (TTR) tester working principle and test procedure

Views :
Update time : 2025-04-02

Senior Technical Engineer at transformer tester manufacturer demiks says, Three-phase transformer turns ratio (TTR) tester is used to verify voltage ratios and winding connections in power transformers. It ensures that the transformer meets the design specifications and detects faults such as short circuits between turns, open windings or incorrect tap settings.

1. Working Principle

The TTR tester applies a low-voltage AC signal to one winding (primary) and measures the induced voltage in the other winding (secondary). The turns ratio (TTR) is calculated as:

Turns Ratio=VPrimaryVSecondaryTurns Ratio=VSecondaryVPrimary

Key Features of a 3-Phase TTR Tester:
✔ Measures phase-to-phase and phase-to-neutral ratios.
✔ Checks vector group (Dyn11, YNd1, etc.).
✔ Detects shorted turns, open circuits, and incorrect tap changers.
✔ Auto-compares results with nameplate values.


2. Testing Procedure

Step 1: Safety Precautions

  • De-energize the transformer and isolate it.

  • Disconnect all external connections (bushings, CTs, etc.).

  • Ground the transformer tank for safety.

Step 2: Select Test Mode

  • Single-Phase Mode (for individual winding pairs).

  • 3-Phase Mode (for complete transformer testing).

Step 3: Connect Test Leads

  • Primary Side (HV): Connect to H1, H2, H3.

  • Secondary Side (LV): Connect to X1, X2, X3.

  • For Delta (Δ) or Wye (Y) windings, follow the correct terminal configuration.

Step 4: Perform TTR Test

  • Apply a low-voltage AC signal (typically 10V–100V).

  • The tester automatically measures:

    • Voltage ratio (TTR) for each phase.

    • Phase displacement (for vector group verification).

Step 5: Compare with Nameplate

  • Acceptance Criteria:

    • Ratio Error: ±0.5% of nameplate value.

    • Phase Angle Deviation: ±1° (for vector group verification).

Step 6: Check Tap Changer (If Applicable)

  • Test at each tap position to ensure proper ratio adjustment.


3. Interpretation of Results

IssuePossible CauseDiagnosis
High Ratio ErrorShorted turns, incorrect tap settingCheck winding resistance
Zero/Infinite RatioOpen winding, broken connectionPerform continuity test
Phase Shift MismatchWrong vector group (e.g., Dyn11 vs. YNd1)Verify nameplate & connections

4. Standards & Best Practices

  • IEEE C57.12.90 (Transformer Testing)

  • IEC 60076-1 (Power Transformers)

  • Test Frequency: During commissioning, after maintenance, or if a fault is suspected.


Recommended TTR Testers

  1. OMICRON CPC 100 (Advanced 3-phase testing)

  2. Megger TTR20 (Portable, high-accuracy)

  3. SebaKMT TOR 10 (For field testing)

The above content is published by demiks, please specify, demiks is a substation equipment manufacturer, specializing in the production of high-voltage tester, Transformer Tester, circuit breaker test equipment, relay tester, SF6 gas analyser, cable fault tester and other products, if you have power test testing needs, please feel free to contact demiks power science and technology limited company or send an email! Give us: contact@demikspower.com 

Related News
Read More >>
Relay Protection Testing and Commissioning Gu Relay Protection Testing and Commissioning Gu
04 .14.2025
Protection Relay Testing & Commissioning GuideProtection relays are critical for
how to test microwave transformer how to test microwave transformer
04 .14.2025
Testing a microwave oven transformer (MOT) requires caution because these transf
how to reset circuit breaker with test button how to reset circuit breaker with test button
04 .14.2025
Resetting a circuit breaker with a Test button (commonly found in GFCI or AFCI b
high voltage cable testing standards high voltage cable testing standards
04 .14.2025
High voltage cable testing standards are critical to ensure the safety, reliabil

Leave Your Message