Determine copper losses (I²R losses) at rated current
Calculate equivalent impedance (Zₛₛ), resistance (Rₛₛ), and reactance (Xₛₛ)
Verify transformer's withstand capability under fault conditions
Provide data for protection relay settings
mermaid复制
graph LR A[3-Phase Variax] -->|Variable Voltage| B[Transformer HV] B -->|Short Circuit| C[LV Terminals] D[Power Analyzer] --> B
E[CT/PT] --> D
Equipment Required:
Variable AC voltage source (0-10% of rated voltage)
Current transformers (CTs) & potential transformers (PTs)
Power analyzer (measures P, I, V, PF)
Temperature sensor (for resistance correction)
Short LV windings using heavy copper busbars (ensure solid connection)
Connect instruments to HV side (test is typically performed from HV side)
Verify all safety interlocks are active
Gradually increase voltage until rated current flows (usually 5-8% of rated V)
Record at steady state:
Input voltage (Vₛₛ)
Current (Iₛₓ = Rated current)
Power (Pₛₛ)
Winding temperature (θ)
Parameter | Symbol | Typical Range (Oil-immersed 10MVA) |
---|---|---|
Short-circuit voltage | Vₛₛ | 5-12% of rated V |
Load loss | Pₛₛ | 0.3-1.2% of rated power |
Impedance | Zₛₛ | 4-10% (distribution), 12-20% (furnace) |
Equivalent impedance (Zₛₛ):
Zss=IratedVssEquivalent resistance (Rₛₛ):
Rss=3×Irated2PssEquivalent reactance (Xₛₛ):
Xss=Zss2−Rss2Rss(75°C)=Rss(θ)×235+θ235+75
Pss(75°C)=3×I2×Rss(75°C)
Result | Possible Causes |
---|---|
High Zₛₛ | Loose connections, winding deformation |
Low Zₛₛ | Shorted turns, incorrect tap position |
High Pₛₛ | Poor conductor quality, eddy current losses |
Unbalanced phases | Damaged winding, core asymmetry |
Use IR goggles during energization (arc flash risk)
Ensure proper shorting bar cross-section (≥1.5× cable area)
Follow IEEE C57.12.90 and IEC 60076-5 standards
Test Data:
10MVA, 33/6.6kV Dyn11 transformer
Vₛₛ = 1800V (5.45% of 33kV)
Iₛₛ = 175A (rated)
Pₛₛ = 85kW at 32°C
Calculations:
Zss=1751800=10.29Ω (9.36% impedance)
Rss=3×175285000=0.925Ω
Corrected to 75°C: Rss(75°C)=1.106Ω, Pss(75°C)=101.6kW
Parameter | Short Circuit Test | Open Circuit Test |
---|---|---|
Winding energized | HV | LV |
Losses measured | Copper (load) | Iron (no-load) |
Voltage applied | Low (5-8%) | Rated |
Industry Tip: Always perform short circuit test before open circuit test to avoid core remanence effects.
Frequency response analysis: Detect winding displacement
Dynamic short-circuit testing: Verify mechanical strength
Thermal imaging: Identify hot spots during test
This test is essential for transformer test equipment nameplate data verification, efficiency calculations, and protection coordination studies. Always refer to factory test reports and IEEE/IEC standards for detailed analyses.