Shanghai DEMIKS Electric Power Technology Co.,LTD

Three Phase Transformer Winding Resistance Test Procedures and Guidelines

Views :
Update time : 2025-03-31

Winding resistance testing is a critical diagnostic test for transformers, helping detect:

  • Loose connections

  • Broken strands in windings

  • Contact issues in tap changers

  • Imbalance between phases


1. Test Equipment

  • Micro-ohmmeter (preferred, with 1µΩ resolution)

  • Kelvin Bridge (DC resistance bridge)

  • Temperature sensor (for correction to 20°C)

  • Test leads with high-current clamps


2. Test Procedure

Step 1: Safety Precautions

✔ De-energize the transformer and ground windings.
✔ Discharge stored energy (inductive kickback).
✔ Verify lockout/tagout (LOTO).

Step 2: Connections

  • Star (Wye) Windings:

    • Measure phase-to-neutral (if accessible) or phase-to-phase and calculate phase resistance.

  • Delta Windings:

    • Measure phase-to-phase and use formulas to derive individual phase resistances.

Connection Diagram

       R1                          R2
      ▲                            ▲
      │                            │
      └────[Transformer]────┘
      ▲                            ▲
      │                            │
      R3                          (Neutral, if Wye)

Step 3: Apply DC Current & Measure

  • Inject 10–50% of rated current (to avoid heating).

  • Wait for stabilization (typically 1–5 minutes).

  • Record resistance (R) + temperature (T).

Step 4: Temperature Correction

  • Convert readings to 20°C for comparison:

    R20°C=Rmeasured×234.5+20234.5+TR20°C=Rmeasured×234.5+T234.5+20

    (For copper windings; use 225 for aluminum)

Step 5: Compare Results

  • Acceptance Criteria (IEEE C57.12.90):

    • Deviation ≤ ±2% between phases.

    • Match factory data within ±5%.


3. Common Issues & Troubleshooting

IssuePossible CauseSolution
High ResistanceLoose connections, broken strandsCheck joints, retorque bolts
Low ResistanceShorted turnsPerform TTR (Turns Ratio Test)
Unbalanced PhasesTap changer misalignmentInspect OLTC/MOLTC contacts

4. Standards & Best Practices

  • IEEE C57.12.90 (Transformer Testing)

  • IEC 60076-1 (Power Transformers)

  • Test at multiple tap positions (for OLTC transformers).

  • Use 4-wire (Kelvin) method to eliminate lead resistance errors.


5. Example Measurement (11kV/433V Transformer)

WindingMeasured (µΩ)Temp (°C)Corrected (20°C, µΩ)
Phase R54030515
Phase Y54530520
Phase B55030525
Deviation< 2% ✅


Key Takeaways

✅ Detects winding defects before failure.
✅ Must be temperature-corrected for accuracy.
✅ Unbalance >2% indicates a problem.

The above content is published by demiks, please specify, demiks is a substation equipment manufacturer, specializing in the production of high-voltage tester, transformer test equipment, circuit breaker test equipment, relay tester, SF6 gas analyser, cable fault tester and other products, if you have power test testing needs, please feel free to contact demiks power science and technology limited company or send an email! Give us: contact@demikspower.com 

Related News
Read More >>
Relay Protection Testing and Commissioning Gu Relay Protection Testing and Commissioning Gu
04 .14.2025
Protection Relay Testing & Commissioning GuideProtection relays are critical for
how to test microwave transformer how to test microwave transformer
04 .14.2025
Testing a microwave oven transformer (MOT) requires caution because these transf
how to reset circuit breaker with test button how to reset circuit breaker with test button
04 .14.2025
Resetting a circuit breaker with a Test button (commonly found in GFCI or AFCI b
high voltage cable testing standards high voltage cable testing standards
04 .14.2025
High voltage cable testing standards are critical to ensure the safety, reliabil

Leave Your Message