Shanghai DEMIKS Electric Power Technology Co.,LTD

how to test a transformer with multimeter

Views :
Update time : 2025-04-15

Testing transformers with a multimeter in a transformer tester helps to verify windings, insulation, and function prior to installation or troubleshooting. The following is a step-by-step guide to testing power transformers, isolation transformers, and small control transformers using a digital multimeter (DMM).


1. Safety Precautions

Disconnect power before testing.
Discharge the transformer (short terminals with a resistor if recently powered).
Wear insulated gloves when handling high-voltage transformers.
Verify the multimeter’s voltage rating matches the transformer.


2. Tools Needed

✔ Digital Multimeter (DMM) – Measures voltage, resistance, and continuity.
✔ Insulation Tester (Megger, optional for HV transformers) – Checks insulation breakdown.


3. Step-by-Step Testing Procedure

A. Identify Transformer Terminals

  • Primary Winding (Input side, e.g., 120V, 240V).

  • Secondary Winding (Output side, e.g., 12V, 24V).

  • Center Tap (if any) – Some transformers have a middle terminal.


B. Test for Open or Shorted Windings (Resistance Check)

  1. Set multimeter to resistance (Ω) mode.

  2. Disconnect all wires from the transformer.

  3. Check primary winding:

    • Place probes on primary terminals.

    • Expected: A few ohms to hundreds of ohms (depends on size).

    • If OL (Open Line) → Winding is broken (faulty).

    • If 0Ω → Shorted winding (faulty).

  4. Check secondary winding:

    • Repeat for secondary side (should read lower resistance than primary).

    • Example: A 12V secondary may read 0.5Ω–5Ω.


C. Test for Short to Ground (Insulation Check)

  1. Set multimeter to highest resistance range (or Megger for HV).

  2. Check primary to core/ground:

    • One probe on primary terminal, the other on transformer core/ground.

    • Expected: OL (no continuity).

    • If resistance < 1MΩ → Insulation failure (leakage).

  3. Repeat for secondary to ground.


D. Test Turns Ratio (Voltage Check, Requires External Power)

  1. Apply a low AC voltage (e.g., 12V) to the primary.

  2. Measure output voltage on secondary.

    • Example: If primary = 120V, secondary = 12V → Ratio = 10:1.

    • If voltage is too low → Shorted turns.

    • If no voltage → Open winding.


E. Check for Overheating (Operational Test)

  1. Reconnect transformer to rated voltage.

  2. Run for 5–10 minutes.

  3. Feel for excessive heat (should be warm, not hot).

  4. If overheating → Possible shorted turns or overload.


4. Common Transformer Faults & Symptoms

FaultMultimeter ReadingSolution
Open windingOL (infinite Ω)Replace transformer
Shorted winding0Ω (or very low Ω)Replace transformer
Shorted to groundLow resistance to coreReplace/rewind
Wrong voltage ratioIncorrect output VCheck windings

5. When to Replace a Transformer?

Open or shorted windings
Burnt smell or visible damage
Excessive humming/vibration
Insulation resistance < 1MΩ


Conclusion

To test a transformer with a multimeter:

Check winding resistance (should not be open or shorted).

Test insulation to ground (should be >1MΩ).

Verify voltage ratio (if possible).

Replace if faulty.


Related News
Read More >>
Relay Protection Testing and Commissioning Gu Relay Protection Testing and Commissioning Gu
04 .14.2025
Protection Relay Testing & Commissioning GuideProtection relays are critical for
how to test microwave transformer how to test microwave transformer
04 .14.2025
Testing a microwave oven transformer (MOT) requires caution because these transf
how to reset circuit breaker with test button how to reset circuit breaker with test button
04 .14.2025
Resetting a circuit breaker with a Test button (commonly found in GFCI or AFCI b
high voltage cable testing standards high voltage cable testing standards
04 .14.2025
High voltage cable testing standards are critical to ensure the safety, reliabil

Leave Your Message