Testing transformers with a multimeter in a transformer tester helps to verify windings, insulation, and function prior to installation or troubleshooting. The following is a step-by-step guide to testing power transformers, isolation transformers, and small control transformers using a digital multimeter (DMM).
Disconnect power before testing.
Discharge the transformer (short terminals with a resistor if recently powered).
Wear insulated gloves when handling high-voltage transformers.
Verify the multimeter’s voltage rating matches the transformer.
✔ Digital Multimeter (DMM) – Measures voltage, resistance, and continuity.
✔ Insulation Tester (Megger, optional for HV transformers) – Checks insulation breakdown.
Primary Winding (Input side, e.g., 120V, 240V).
Secondary Winding (Output side, e.g., 12V, 24V).
Center Tap (if any) – Some transformers have a middle terminal.
Set multimeter to resistance (Ω) mode.
Disconnect all wires from the transformer.
Check primary winding:
Place probes on primary terminals.
Expected: A few ohms to hundreds of ohms (depends on size).
If OL (Open Line) → Winding is broken (faulty).
If 0Ω → Shorted winding (faulty).
Check secondary winding:
Repeat for secondary side (should read lower resistance than primary).
Example: A 12V secondary may read 0.5Ω–5Ω.
Set multimeter to highest resistance range (or Megger for HV).
Check primary to core/ground:
One probe on primary terminal, the other on transformer core/ground.
Expected: OL (no continuity).
If resistance < 1MΩ → Insulation failure (leakage).
Repeat for secondary to ground.
Apply a low AC voltage (e.g., 12V) to the primary.
Measure output voltage on secondary.
Example: If primary = 120V, secondary = 12V → Ratio = 10:1.
If voltage is too low → Shorted turns.
If no voltage → Open winding.
Reconnect transformer to rated voltage.
Run for 5–10 minutes.
Feel for excessive heat (should be warm, not hot).
If overheating → Possible shorted turns or overload.
Fault | Multimeter Reading | Solution |
---|---|---|
Open winding | OL (infinite Ω) | Replace transformer |
Shorted winding | 0Ω (or very low Ω) | Replace transformer |
Shorted to ground | Low resistance to core | Replace/rewind |
Wrong voltage ratio | Incorrect output V | Check windings |
Open or shorted windings
Burnt smell or visible damage
Excessive humming/vibration
Insulation resistance < 1MΩ
To test a transformer with a multimeter:
Check winding resistance (should not be open or shorted).
Test insulation to ground (should be >1MΩ).
Verify voltage ratio (if possible).
Replace if faulty.