Insulation Resistance Test (Megger Test)
DC Hi-Pot (High Potential) Test
Partial Discharge (PD) Test
Tan Delta (Dissipation Factor) Test
VLF (Very Low Frequency) Test
Time Domain Reflectometry (TDR) for Fault Location
Sheath Integrity Test (For Metallic Sheathed Cables)
Impulse Testing (Surge Testing)
✔ De-energize the cable and follow LOTO (Lockout-Tagout) procedures.
✔ Verify proper grounding before testing.
✔ Use appropriate PPE (insulated gloves, safety barriers).
✔ Check test equipment calibration status.
Purpose: Measures insulation quality (in MΩ).
Equipment: Insulation resistance tester (5kV or 10kV Megger).
Procedure:
Disconnect cable from both ends (switchgear & transformer).
Discharge any residual voltage using a grounding rod.
Connect the Megger:
Line terminal → Cable conductor.
Earth terminal → Cable sheath/armor.
Apply test voltage (typically 500V to 10kV DC) for 1 minute.
Record insulation resistance value (should be > 1000 MΩ/km for new cables).
Discharge the cable after testing.
Acceptance Criteria:
> 100 MΩ (Older cables)
> 1000 MΩ (New cables)
Purpose: Checks insulation strength under high DC voltage.
Equipment: DC Hi-Pot tester (up to 2x rated voltage).
Procedure:
Ensure cable is fully discharged.
Connect:
Positive terminal → Cable conductor.
Negative terminal → Ground/sheath.
Gradually increase voltage (step-up method):
Step 1: 25% of test voltage, hold for 1 min.
Step 2: 50% of test voltage, hold for 1 min.
Step 3: 75% of test voltage, hold for 1 min.
Step 4: 100% of test voltage, hold for 15 min.
Monitor leakage current (should stabilize).
If current spikes or breakdown occurs, stop the test.
Test Voltage (IEC 60502 Standard):
Cable Rating (kV) | Test Voltage (DC, kV) |
---|---|
11 kV | 22 kV (2x rated) |
33 kV | 66 kV |
Acceptance Criteria:
No breakdown or sudden current surge.
Leakage current should stabilize (no continuous rise).
Purpose: Detects insulation defects using 0.1 Hz AC (alternative to DC Hi-Pot).
Equipment: VLF tester (up to 3x rated voltage).
Procedure:
Connect VLF tester to the cable conductor.
Apply 0.1 Hz AC voltage in stages (similar to Hi-Pot).
Hold at final voltage (3U₀) for 15-60 min.
Monitor tan delta (dissipation factor) for insulation health.
Advantages:
Less damaging than DC for aged cables.
Detects water trees & partial discharges.
Purpose: Locates internal voids or defects in insulation.
Equipment: PD detector, coupling capacitor, HV source.
Procedure:
Apply AC voltage slightly above operating level.
Use high-frequency CT sensors to detect PD signals.
Analyze PD magnitude (pC) and phase-resolved patterns.
Acceptance Criteria:
< 10 pC (New cables)
< 100 pC (Older cables, monitor trend)
Purpose: Measures insulation dielectric losses.
Equipment: Tan delta bridge, HV source.
Procedure:
Apply AC voltage at power frequency (50/60 Hz).
Measure loss angle (δ) and calculate tan δ = (Iᵣ/I꜀).
Acceptance Criteria:
< 0.5% (Healthy insulation)
> 1% (Degraded insulation – further investigation needed)
✔ Insulation breakdown (Hi-Pot test failure).
✔ Water ingress (VLF/Tan Delta test).
✔ Partial discharges (PD test).
✔ Shield/sheath damage (TDR test).
⚠ Always discharge cables before & after testing.
⚠ Use proper grounding to avoid residual voltage hazards.
⚠ Follow IEEE 400 & IEC 60502 standards.
⚠ Never exceed recommended test voltages.
Regular HV cable testing ensures long-term reliability and prevents unexpected failures. Key tests include:
✅ Megger (Insulation Resistance)
✅ DC Hi-Pot (Dielectric Strength)
✅ VLF (Aged Cable Testing)
✅ Partial Discharge (Early Fault Detection)
The above content is published by demiks, please specify, demiks is a substation equipment manufacturer, specializing in the production of high-voltage tester, transformer tester, circuit breaker test equipment, relay tester, SF6 gas analyser, cable fault tester and other products, if you have power test testing needs, please feel free to contact demiks power science and technology limited company or send an email! Give us: contact@demikspower.com