Shanghai DEMIKS Electric Power Technology Co.,LTD

how to test a circuit breaker without power

Views :
Update time : 2025-04-10

According to expert research on relevant circuit breaker testers, testing circuit breakers without power (disconnect) is critical for maintenance, troubleshooting and safety verification. The following is a step-by-step approach to testing different types of circuit breakers (CBs) using both manual and instrument-based techniques.


1. Safety Precautions

✅ De-energize the circuit – Ensure the breaker is isolated from all power sources (verify with a voltage tester).
✅ Discharge capacitors – Some systems (e.g., VCBs) may store residual energy.
✅ Wear insulated gloves & PPE – Even when off, accidental contact with live parts must be prevented.


2. Visual Inspection

Before electrical testing, perform a physical check:

  • Contacts & Arc Chutes – Look for burns, cracks, or carbon buildup.

  • Mechanical Linkages – Ensure smooth operation (no sticking or misalignment).

  • Terminals – Check for loose connections or corrosion.


3. Manual Operation Test (Mechanical Function)

  • For Molded Case Circuit Breakers (MCCBs) & Air Circuit Breakers (ACBs):

    • Turn the breaker ON/OFF manually – Should move smoothly without excessive force.

    • Trip Test: Use the manual trip button (if available) to verify the mechanism releases.

  • For Oil/Gas Circuit Breakers:

    • Check operating mechanism springs, hydraulic/pneumatic pressure (if applicable).


4. Insulation Resistance Test (Megger Test)

Purpose: Checks for insulation degradation between phases and ground.
Equipment Needed: Insulation resistance tester (Megger, 500V–5kV DC).

Procedure:

  1. Disconnect all cables from the breaker.

  2. Set Megger to 1000V DC (for LV breakers) or 5kV DC (for HV breakers).

  3. Test between:

    • Phase-to-Phase (A-B, B-C, C-A) – Should read >100 MΩ.

    • Phase-to-Ground (A-E, B-E, C-E) – Should read >10 MΩ.

  4. Failures:

    • <1 MΩ = Moisture/contamination.

    • <0.5 MΩ = Severe insulation damage.


5. Contact Resistance Test (Micro-Ohmmeter)

Purpose: Measures resistance across closed contacts (high resistance = overheating risk).
Equipment Needed: Ductor tester (micro-ohmmeter).

Procedure:

  1. Close the breaker manually (ensure contacts are engaged).

  2. Connect tester to line & load terminals.

  3. Measure resistance:

    • LV Breakers (MCCB/ACB): <50 µΩ (new), <100 µΩ (used).

    • HV Breakers (VCB/SF6): <200 µΩ.

    • Acceptable Range:

    • High resistance (>500 µΩ): Indicates pitting, oxidation, or loose connections.


6. Timing & Motion Analysis (For HV Breakers)

Purpose: Checks open/close time, synchronism, and contact travel.
Equipment Needed: CB analyzer (e.g., Megger, OMICRON, Doble).

Tests Performed:

TestAcceptable RangeFailure Indication
Closing Time<50 ms (typical)Worn mechanism
Opening Time<30 ms (typical)Slow trip coil
Contact TravelMatch manufacturer specsMisalignment
Coil CurrentWithin rated valuesWeak solenoid

7. SF6 Gas Pressure Test (For Gas CBs)

  • Check pressure gauge – Should be in the green zone.

  • Leak test – Use an SF6 gas detector (if pressure drops abnormally).


8. Secondary Injection Test (Protection Relay Verification)

Purpose: Tests trip coil, protective relays, and control circuits without primary current.
Equipment Needed: Secondary injection test set.

Procedure:

  1. Inject a simulated fault current (e.g., 5A for overcurrent relay).

  2. Verify:

    • Relay picks up & sends a trip signal.

    • Breaker mechanically trips.


9. Summary: Key Tests for Different Breaker Types

TestMCCB/ACBVCBSF6 CBOil CB
Insulation (Megger)
Contact Resistance
Timing Analysis
SF6 Gas Check

10. Common Faults & Solutions

SymptomPossible CauseSolution
High contact resistanceBurnt contacts, oxidationClean/replace contacts
Slow trippingWeak trip coil, mechanical wearLubricate/replace parts
Insulation failureMoisture ingress, agingDry or replace breaker

Conclusion

Testing a circuit breaker without power involves:

  1. Visual & mechanical checks (operation, linkages).

  2. Insulation resistance test (Megger).

  3. Contact resistance test (Micro-ohmmeter).

  4. Timing tests (for HV breakers).

  5. Secondary injection (relay verification).

Need more details? Ask about:

  • How to test a vacuum interrupter?

  • Differences between MCCB, ACB, VCB testing?

  • SF6 gas handling safety precautions?

The above content is published by demiks, please specify, demiks is a substation equipment manufacturer, specializing in the production of high-voltage tester, transformer tester, circuit breaker test equipment, relay tester, SF6 gas analyser, cable fault tester and other products, if you have power test testing needs, please feel free to contact demiks power science and technology limited company or send an email! Give us: contact@demikspower.com 


Related News
Read More >>
Relay Protection Testing and Commissioning Gu Relay Protection Testing and Commissioning Gu
04 .14.2025
Protection Relay Testing & Commissioning GuideProtection relays are critical for
how to test microwave transformer how to test microwave transformer
04 .14.2025
Testing a microwave oven transformer (MOT) requires caution because these transf
how to reset circuit breaker with test button how to reset circuit breaker with test button
04 .14.2025
Resetting a circuit breaker with a Test button (commonly found in GFCI or AFCI b
high voltage cable testing standards high voltage cable testing standards
04 .14.2025
High voltage cable testing standards are critical to ensure the safety, reliabil

Leave Your Message